| Type |
Terminal |
Function Name |
Description |
| Control signal |
1 |
Forward run / Stop |
Forward run when closed, stop when opened |
Terminal 3 ~ 8
are Multifunctional terminals |
| 2 |
Reverse run / Stop |
Reverse run when closed, stop when opened |
| 3 |
External fault input |
Fault when close, normal when opened |
| 4 |
Fault reset |
Reset when closed |
| 5 |
Master / Auxiliary speed switch |
Auxiliary frequency commandn when closed |
| 6 |
Multi-step speed command 2 |
Effective when closed |
| 7 |
JOG instruction |
Effective when closed |
| 8 |
Coasting to stop |
Effective when closed |
| 11 |
Switch input common terminal |
|
| Analog input signal |
15 |
Speed command power supply +15V |
Speed command sets the power supply terminal as +15V |
| 33 |
Speed command power supply -15V |
Speed command sets the power supply terminal as -15V |
| 13 |
Master speed frequency reference |
0~10V/100% frequency; -10~+10V/100%~+100% frequency; 4~20mA/100% frequency |
| 14 |
| 16 |
Auxiliary speed frequency reference |
0~10V/100% frequency; -10~+10V/-100%~+100% frequency |
| 17 |
Common terminal |
Terminal 13,14 are speed command common terminals |
| 12 |
Shield wire ground terminal |
Shield cover of connecting shield wire |
| Switch output signal |
9 |
Operating signal |
Closed while operating |
contact output |
| 10 |
| 25 |
Zero speed output |
Closed below the min. frequency |
Multi-function analog value monitoring |
| 26 |
Speed arriving output |
Set as low potential level within frequency ±2Hz |
| 27 |
Terminal 25,26 are common terminals |
|
| 18 |
Error contact output |
Fault when terminal 18 and 19 closed
Fault when terminal 18 and 19 opened |
| 19 |
| 20 |
| Analog output signal |
21 |
Output frequency |
0~10V/100% frequency |
Multi-function analog value monitoring |
| 22 |
Analog input common ground |
| 23 |
Output current |
0~5V/100% current |
Multi-function
contact output |